Water Conservation Strategies for Australian Cooling Towers

Writer: Gerry Wagner
Gerry Wagner
27 minutes ago
7 min read

Makeup water has been running like a process line since the last heatwave. Conservation is the basin and the blowdown, not a bigger tower. We measure cubic metres in before we talk about a new cell.


Cooling tower water conservation on an Australian site is not a campaign to stop evaporation. Evaporation is the heat sink. The work is to stop every other litre that never carried heat, and to stop the fill and the basin turning so foul that operators open the dump to keep approach from walking off.


Where Makeup Water Actually Leaves the Circuit


Makeup has four exits: evaporation, blowdown, drift, and leaks or overflows. Only the first one is doing the duty.


Evaporation follows the heat load. A tower rejecting a given kilowatt will evaporate a given mass of water, wet-bulb and approach sitting where they sit. You do not conserve that water by throttling the fan into a high-approach mess. You conserve it by keeping the fill clean so the same duty does not need extra hours, extra cells, or a panic dump.


Blowdown is the controllable stream. It exists to hold dissolved solids below the point where scale, corrosion or biofouling take the pack. Timer blowdown and “open it until the basin looks better” are how plants double makeup without moving a single extra joule. Plate heat exchangers stay in the same work pack when the plates and gaskets are on duty.


Drift should be a mist you cannot see from the gantry. Torn eliminators, missing seals at the fan deck, and high basin levels that wet the eliminators turn drift into a second blowdown you never metered.


Leaks and overflows are the silent ones. A stuck float, a cracked basin joint, a dump valve that does not seat, a winter drain left cracked, all of it reads as makeup. Fit meters on makeup and blowdown before you argue about cycles Industrial radiators


Cycles of Concentration the Fill Can Live With


Cycles of concentration are makeup volume divided by blowdown volume, once evaporation and drift are in the balance. Raise cycles and you throw less water. Raise them past what the water and the fill can stand and you grow scale in the pack, raise dP on the spray, and lose approach Cooling towers on the same circuit change the water chemistry the pack has to live with. Fans and pumps on that circuit are logged with the exchanger, not after the fact.


The limit is the water, not a slogan. Hardness, silica, chlorides, sulphates and the inhibitor package set the ceiling. A bore with silica will not hold the same cycles as a soft town supply. Seawater duty is a different plant: once-through or very low cycles, different metallurgy, different fill, and conservation means not leaking the circuit into the yard rather than chasing ten cycles.


Hold cycles with conductivity control tied to a blowdown valve that actually strokes. A probe sitting in sludge, or a valve that weeps, will either over-blow or under-blow. Over-blow wastes water. Under-blow scales the fill, and then someone opens the dump for a week.


Log cycles against basin conductivity, makeup meter and blowdown meter on the same shift. If the three disagree, fix the instruments before you change setpoints.


Blowdown Setpoints Versus Chemistry That Holds


Opening blowdown is the cheapest-looking response to cloudy basin water and rising approach. It is also the fastest way to wreck a water balance.


If the basin is dirty, the dirt is usually suspended solids, biofilm or broken fill, not “too many cycles.” Dumping does not replace filtration or a proper biocide programme. It replaces treated water with more makeup, which often brings more hardness and more nutrients.


Inhibitor Dispersant and Oxidising or Non Oxidising

Inhibitor, dispersant and oxidising or non-oxidising biocide have to match the metallurgy, the fill polymer and the hold-up time. Starving the programme and compensating with blowdown is how plants run high makeup all summer and still CIP the plate pack every shutdown because the cooling water side is a biofilm farm.


Set blowdown from a conductivity (or chloride) limit that the treatment vendor and the fill supplier both accept. Then treat that limit. If you cannot hold the limit without scale, the answer is better pretreatment or lower cycles, not a valve locked open.


Closed Loop Cooling Systems When Open Towers Waste the Site


Some duties should not see an open basin at all. Process fluid that cannot take contamination, sites on tight water licences, dusty yards that sandblast the fill, or plants that already fight Legionella with dump-and-fill habits, all waste more water than the heat load requires.


Closed loop cooling systems put the process on a treated, sealed circuit, glycol or inhibited water, and reject heat through a plate pack, a shell and tube, or a closed-circuit cooler. The open tower, if it remains, only sees secondary water you can run at honest cycles. In some plants the open tower comes off altogether and the duty moves to air-cooled or adiabatic gear sized for the wet-bulb you actually have.


That isolation also protects gaskets and plate packs. Tower water loaded with solids and oxidiser eats elastomer and fouls channels. A closed process loop with a dedicated exchanger lets you CIP the dirty side on a planned window instead of living with rising dP until the unit trips.

We run that next outage with Allied Heat Transfer against the duty already on the plant.


When the open circuit cannot hold cycles, or the licence will not wear the makeup, the path is turnkey cooling systems that close the loop and take evaporative loss off the water balance rather than arguing with a basin that was never going to be clean.


Drift, Leaks and the Basin You Cannot See From the Gantry




Basin level control is water conservation hardware. A float that hunts, a probe coated in scale, or an equalising line blocked between cells will overflow one cell while another runs a vortex into the pump suction. Overflow is a blowdown you did not choose.


Look under the tower. Stains on the slab, a wet sump pump that never used to run, and makeup that continues at night with fans off and load down, are leaks. Repair them before you return cycles. A cracked FRP joint or a failed grommet will beat any chemistry change.


Winter dumps and “we drain for maintenance and refill from the mains” habits destroy conservation numbers. Isolate, drain only the volume you must, and refill through a meter. If freeze protection is the reason, that is a closed-loop or glycol conversation, not a weekly dump cooling tower water conservation.


Sidestream Filtration Before the Next CIP


Suspended solids grind fill, seed scale, and load the cooling-water side of every exchanger on the loop. Sidestream filtration, a sand, multimedia or automatic strainer loop on a fraction of circulating flow, cuts basin turbidity without opening blowdown. It sits with Fans and pumps.


Sweep the basin. Dead legs, round basins with no velocity, and fill that sheds slime all drop solids where the pump cannot pick them up. A dirty basin makes every conductivity probe a liar and every plate packs a filter


The plate pack tells the truth the tower hides. Rising dP on the cooling-water side, approach walking out on the process side, and more frequent CIP are the bill for a tower that is using water as a sewer. Gasket life drops when you CIP often and when oxidiser residuals sit high because someone is fighting biofilm with chlorine instead of with filtration and a clean fill


Put Filtration in Before the Next Clean

Put filtration in before the next clean, not after. A CIP on a pack that will be re-fouled in a fortnight is labour, gasket risk and downtime. It is not conservation.


Approach and Fan Load As Water Drivers


Approach is the gap between cold-water temperature and ambient wet-bulb. Packed fill, dry spots, blocked nozzles and uneven water distribution all worsen approach. Worse approach means more fans, more cells, longer hours, and sometimes a second tower that evaporates water the first tower should have rejected.


dP on the air side and the spray system are your early warnings. High air-side dP is fill or eliminator blockage. High spray dP with poor distribution is nozzles or laterals. Both waste water because the tower is no longer doing the heat transfer the makeup calculation assumed.


Do not chase water by starving airflow. A fan bank in bypass with a dirty fill will push heat back into the process, and the plant will compensate with more circulation, more hours, and more evaporation at a worse approach. Clean the fill, restore distribution, then set fans on wet-bulb and load, not on a fixed damper story from 2014.


Oil coolers, jacket water and condenser loops all feel this. If the cooling-water temperature into those units is high because the tower cannot make an approach, you will see process trips and someone will open more makeup “to help.” It does not help. The water is already in the basin. The fill is not working.


What Australian Water Rules Expect From the Plant


Makeup, bore take, trade waste and cooling-tower registration sit under state rules, not under a vendor datasheet. In Western Australia the licensing, restriction and department pages on Water Corporation are the place to read take limits, discharge expectations and the notices that land on a plant before you change a blowdown destination or a bore allocation.


Do not assume a conductivity dump to stormwater is fine because it always has been. Do not assume a bore can cover a summer of open blowdown because last year was mild. Meter first, then argue the licence with numbers.


Legionella control and water conservation are not opposites if the basin is filtered, the fill is intact and the biocide residual is controlled. They become opposites when the only tool on the board is a dump valve.


Dust, pollen, bushfire ash and coastal salt all load Australian towers harder than a catalogue fill photo. Specify fill and eliminators for the air you actually have, and budget a wash or a replacement interval that matches the yard, not a European brochure.


Checks Before the Next Shutdown or Clean


Before the next shutdown, read three numbers on the same day: makeup cubic metres, blowdown cubic metres, and basin conductivity. Calculate cycles. If you cannot calculate cycles, you do not have a conservation programme. You have a hose.


Inspect fill from the access door, not from the ground. Photograph dry spots, scale thickness, collapsed blocks and biological slime. Check nozzles, laterals, eliminators and the blowdown valve stroke. Pull the conductivity probe and look at the tip.


On the exchangers, log cooling-water dP and process approach now, not after the pack is open. That pair tells you whether tower water quality is already eating the plate pack. If CIP is due, sample the debris. Scale chemistry from the pack should match what you believe the tower water is doing. If it does not, the treatment story is wrong.


Speak with us about the pack on that unit before the next shutdown.books the next clean. Bring those photos and the three numbers to the shutdown meeting. That is the difference between another dump-and-hope and a tower that only evaporates what the load actually requires.



 
 